Figure 305: LEVEL MAXIMUM RUN DISTANCE Menu
Scroll right and press Save.
18.4.2 NTS Buffer Distance Up and Down
An NTS alarm may be generated in any direction during normal mode of operation. When this
occurs, the NTS buffer distance needs to be increased
The following procedure describes how to set the NTS buffer distance up and down.
Navigate to MAIN MENU | SETUP | HYDRO. See Figure 60.
From the HYDRO SETUP menu, scroll and select NTS Buffer Distance Up or NTS Buffer
Distance Down.
Figure 306: HYDRO SETUP Menu – NTS Buffer Distance Up or Down
From the NTS BUFFER DISTANCE UP or NTS BUFFER DISTANCE DOWN menu, enter the
buffer distance.
Figure 307: NTS BUFFER DISTANCE UP Menu
Figure 308: NTS BUFFER DISTANCE DOWN Menu
Scroll right and press Save.
18.4.3 Destination and Relevel Offsets
There is some delay at the end of a run between cutting the leveling speed valve and the
coming to a stop. By default, the user may see the car overshoot its destinations and relevel