Hydro:Evolved User Manual
October 2022 © 2022 Smartrise Engineering, Inc. All Rights Reserved Page 255
31.3.3.1 Main or Alternate
The car travels to the main landing when smoke has been detected. If configured and the
smoke is on that floor, the car travels to an alternated landing.
The following procedure describes if the car travels to the main or alternate designated landing
when smoke has been detected.
Navigate to MAIN MENU | SETUP | FIRE. See Figure 56.
From the FIRE SERVICE menu, scroll and select Main Smoke.
Figure 472: FIRE SERVICE Menu Main Smoke
From the MAIN SMOKE menu, scroll and select Main or Alt.
Figure 473: MAIN SMOKE Menu Main or Alt
From the USE ALT FLOOR menu, scroll and select if the main or alternate floor is
configured for main smoke.
Figure 474: USE ALT FLOOR Menu
Scroll right and press Save.
31.3.3.2 Flash Fire Hat
If the fire flash hat been enabled during main smoke, a fire hat symbol on the panel flashes
when smoke has been detected.
The following procedure describes how to enable the flash fire hat.
Navigate to MAIN MENU | SETUP | FIRE. See Figure 56.
From the FIRE SERVICE menu, scroll and select Main Smoke. See Figure 472.

Table of Contents

Other manuals for Smartrise HYDRO:EVOLVED

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Smartrise HYDRO:EVOLVED and is the answer not in the manual?

Smartrise HYDRO:EVOLVED Specifications

General IconGeneral
BrandSmartrise
ModelHYDRO:EVOLVED
CategoryController
LanguageEnglish

Related product manuals