Hydro:Evolved User Manual
Page 188 © 2022 Smartrise Engineering, Inc. All Rights Reserved October 2022
From the HYDRO SETUP menu, scroll and select Battery Test Time.
Figure 342: HYDRO SETUP Menu Battery Test Time
From the BATTERY TEST TIME menu, enter the time the controller searches for a battery
fault.
Figure 343: Battery Test Time Menu
Scroll right and press Save.
18.6 Jack Resync Time
Jack resync is required for hydro elevators that have dual jacks. Over time, the jacks can get out
of sync, causing one to be higher than the other and making the car off level. A resync
operation is done to remove all the oil from both jack cylinders which synchronizes the plungers
back to the same level.
This is normally done as a timed operation. The mechanic sets a time (for example, 3:00 AM)
when the car shall perform a resync operation.
The following procedure describes how to set the jack resync time.
Navigate to MAIN MENU | SETUP | HYDRO. See Figure 60.
From the HYDRO SETUP menu, scroll and select Jack Resync Time.
Figure 344: HYDRO SETUP Menu Jack Resync Time

Table of Contents

Other manuals for Smartrise HYDRO:EVOLVED

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Smartrise HYDRO:EVOLVED and is the answer not in the manual?

Smartrise HYDRO:EVOLVED Specifications

General IconGeneral
BrandSmartrise
ModelHYDRO:EVOLVED
CategoryController
LanguageEnglish

Related product manuals