Table 35: TX Matrix and TX Matrix Plus Router Chassis Component Alarm
Conditions (continued)
Alarm
SeverityRemedyAlarm Condition
Chassis
Component
Yellow• Check the room
temperature.
• Check the air filter
and replace it.
• Check the air flow.
• Check the fan.
The chassis temperature
exceeded 55 degrees C, the
fans turned on to full speed,
and one or more fans have
failed.
Temperature
Yellow• Check the room
temperature.
• Check the air filter
and replace it.
• Check the air flow.
• Check the fan.
The chassis temperature
exceeded 65 degrees C and
the fans have been turned on
to full speed.
Red• Check the room
temperature.
• Check the air filter
and replace it.
• Check the air flow.
• Check the fan.
The chassis temperature
exceeded 65 degrees C and a
fan failed. If this condition
persists for more than 4
minutes, the router shuts
down.
Red• Check the room
temperature.
• Check the air filter
and replace it.
• Check the air flow.
• Check the fan.
Chassis temperature
exceeded 75 degrees C. If this
condition persists for more
than 4 minutes, the router
shuts down.
RedFor technical support,
open a support case
using the Case Manager
link at
http://www.juniper.net
/support/ or call
1-888-314-JTAC (within
the United States) or
1-408-745-9500
(outside the United
States).
The temperature sensor
failed.
Display Error Messages in the Messages Log File
Purpose To determine the details of the error messages in the Messages Log File.
Action To display router component error messages in the messages system log file, use the
following command: