4.15.2 SITOP modules for the PCU 50.5
Suitable SITOP UPS modules
SITOP UPS modules can continue operation of a PC system temporarily if a power failure
occurs and/or shut down the system correctly.
In conjunction with the PCU base software, all specific applications are taken into account (e.g.
HMI software) with the USVShutdown.bat component.
Safe shutdown after a power failure of the PCU 50.5 as delivered takes approximately 20
seconds. For a typical power consumption of approx. 60 W, a capacitor-buffered UPS with an
energy storage device of 2.5 kW is recommended for a PCU 50.5. If longer buffer times are
required, then several expansion modules can be connected in a cascade connection.
Example of a SITOP UPS module that can be used (USB):
SITOP 500S (15 A / 2.5 kWs capacitor)
Article no.: 6EP1933-2EC41
Example of a SITOP UPS with Ethernet/PROFINET interface that can be used:
SITOP UPS1600 starter kit
DC-UPS SITOP UPS1600 24V DC/10A
SITOP UPS1100 3.2 AH battery module
Article No.: 6EP4134-3AB00-2AP0
Note
Information about the test environment for machine OEMs
The functionality has been tested in the standard configuration with the PCU base software.
When installing add-on or OEM software components, you must check the shutdown
procedure of the entire system and adapt the factory setting (180 seconds).
See: Parameterizing a delay time for quitting the HMI software (Page 57)
Further information
Information about available SITOP UPS modules is given in the catalog or in the Internet:
Service & Support Portal: SINUMERIK PCU 50.5: Use of an uninterruptible power supply
(http://support.automation.siemens.com/WW/view/en/90142681)
Service & Support Portal: Typical values for an operator station with PCU 50.5 Windows 7
(http://support.automation.siemens.com/WW/view/en/76773241)
SITOP Selection Tool (http://www.siemens.com/sitop-selection-tool) (Tool for the selection
of a SITOP UPS module)
Catalog KT 10.1 Power supply SITOP
SIEMENS Industry Mall > 24 V DC Uninterruptible Power Supplies (https://
eb.automation.siemens.com/mall/en/US/Catalog/Products/7010117)
Configuration of the system
4.15 Configuring the SITOP UPS module for use with the PCU Base Software
PCU Base Software (IM10)
Commissioning Manual, 12/2017, 6FC5397-1DP40-6BA1 53

Table of Contents

Other manuals for Siemens SINUMERIK ONE MCP 2400.4c

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK ONE MCP 2400.4c and is the answer not in the manual?

Siemens SINUMERIK ONE MCP 2400.4c Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK ONE MCP 2400.4c
CategoryControl Systems
LanguageEnglish

Related product manuals