Procedure
1. Call the SITOP UPS Manager.
2. Change to "Software configuration > Buffer mode".
3. Make the following settings:
Activate the checkbox "Start application on power failure" - and there, enter the path of
USVShutdown.bat:
C:\Program Files (x86)\Siemens\MotionControl\siemens\sinumerik\hmi\base
\USVShutdown.bat
When required, configure the wait time until the HMI software is terminated by
USVShutdown.bat (factory setting = 180 seconds).
Note
Information about the test environment for machine OEMs
The "SITOP UPS" function has been tested in the default configuration with the PCU
base software. When installing add-on or OEM software components, you must check
the shutdown procedure of the entire system and adapt the factory setting.
To do this, enter the wait time in seconds as command line parameter:
Syntax: <Pfad>\USVShutdown.bat -<Time in seconds>
Example: C:\Program Files (x86)\Siemens\MotionControl\siemens\sinumerik\hmi\base
\USVShutdown.bat -180
4. Confirm the settings with "Configuration changed, restart application now".
4.15.4 Hardware configuration of the SITOP UPS module
Buffering parameterization
The UPS module can be used to select whether buffering should be completed after a
predetermined period of time or not until the accumulator’s lowest discharge threshold (=
maximum buffer time) has been reached. Both buffering parameterizations result from this.
"Maximum buffer time" mode
This mode enables the system to be shut down in a time-optimized manner. The UPS module
is synchronized with the shutdown of the operating system. Buffering is maintained until the
operating system has been shut down. The operating system must shut down within a
maximum of five minutes (including all applications). Otherwise, the UPS module buffers for
the maximum buffer time (dependent on the accumulator state).
Required settings on the UPS module (USB interface)
On - Off
1 +2V
Cut-in threshold
+22V fixed
2 +1V
3 +0.5V
Configuration of the system
4.15 Configuring the SITOP UPS module for use with the PCU Base Software
PCU Base Software (IM10)
60 Commissioning Manual, 12/2017, 6FC5397-1DP40-6BA1

Table of Contents

Other manuals for Siemens SINUMERIK ONE MCP 2400.4c

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK ONE MCP 2400.4c and is the answer not in the manual?

Siemens SINUMERIK ONE MCP 2400.4c Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK ONE MCP 2400.4c
CategoryControl Systems
LanguageEnglish

Related product manuals