Depending on the topology, the following actions must be performed on the TM120:
1. TM120 between the Motor Module and the SMx Sensor Module
This TM120 evaluates four KTYs => sensor types must be selected by Servo-p4610/TM-
p4100. The associated temperature is output by servo-r4620/TM120-r4105.
2. TM120 directly on the Line Module
This TM120 evaluates four PTCs => sensor types must be selected by TM-p4100. The
associated temperature is output by servo-r4105.
Setting the threshold values in the PTC context:
TM120-p4102[x]=251 => evaluation Off
TM120-p4102[x]=120 => evaluation On
Assignment of the TM120 response using fault propagation on the drive => setting of
the propagation by servo-p0609=BICO:<object number>TM120:4105.0
Assignment of the alarms to the motor
The occurring error messages are assigned to the motors as follows:
Temperature
channel on the TM120 in series connection with Motor Modules and encoders:
Alarm 207015 <location>drive: Motor temperature sensor warning
Alarm 207016 <location>drive: Motor temperature sensor fault
Alarm 235920 <location>TM: Temperature sensor channel 0 error
In this case, the output message with reference to the motor and to the temperature
component shows the relevant motor.
Temperature channel on the TM120 directly to the Line Module:
Alarm 235207 <location>TM: Temperature fault/alarm threshold channel 0 exceeded
Special feature with PTC:
TM120-r4105 = -50 temperature is below the nominal response temperature
TM120-r4105 = 250 temperature is above the nominal response temperature
In this case, a message is output only with reference to the temperature component.
The affected motor can be determined from the information concerning the TM120.
5.1.10 Exchanging process data
Logical I/O address of drive
The I/O address informs the NC of the data area via which data is cyclically exchanged between
the drive and the Control Unit:
I/O address of the drive
I/O address of the Control Unit
Telegram type
Commissioning the drive
5.1 Commissioning the drive
CNC commissioning
128 Commissioning Manual, 10/2015, 6FC5397-3DP40-5BA3

Table of Contents

Other manuals for Siemens SINUMERIK 828D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK 828D and is the answer not in the manual?

Siemens SINUMERIK 828D Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK 828D
CategoryControl Systems
LanguageEnglish

Related product manuals