C4 User Manual
October 25, 2021 ©2021 Smartrise Engineering, Inc. All Rights Reserved Page 291
3. From the MAIN SMOKE menu, scroll and select Flash Fire Hat.
Figure 559: MAIN SMOKE Menu – Flash Fire Hat
4. From the MAIN: FLASH FIRE HAT menu, scroll and select On.
Figure 560: MAIN: FLASH FIRE HAT Menu
5. Scroll right and press Save.
33.3.3.3 Shunt Trip
A shunt output is designed to trip a breaker shutting off the main power to the controller in
case of a fire in the main lobby.
The following procedure describes how to set up the parameters in case smoke is detected in
the main lobby.
1. Navigate to MAIN MENU | SETUP | FIRE. See Figure 57.
2. From the FIRE SERVICE menu, scroll and select Main Smoke. See Figure 556.
3. From the MAIN SMOKE menu, scroll and select Shunt Trip.
Figure 561: MAIN SMOKE Menu – Shunt Trip
4. From MAIN: SHUNT ON RECALL menu, scroll and select On.
.
Figure 562: MAIN: SHUNT ON RECALL Menu
5. Scroll right and press Save.