C4 User Manual
October 25, 2021 ©2021 Smartrise Engineering, Inc. All Rights Reserved Page 307
2. From the FIRE SERVICE menu, scroll and select Advanced Configuration.
Figure 607: FIRE SERVICE Menu – Advance Configurations
3. From the SMOKE CONFIGURATION menu, scroll and select if the parameter is ON or
OFF.
NOTE: The name of the parameter scrolls to the left.
Figure 608: SMOKE CONFIGURATION Menu
4. Scroll right and press Save.
33.4 Flood
Flooding can occur due to natural disasters or under other occurrences, for example, broken
pipes. When a sensor detects flooding, an alarm is set off and logged.
If this sensor is active, the elevator is limited to traveling to floors above the flood floor set by
the user.
33.4.1 Number of Floors
When flooding has been detected, the parameter set for the flood sensor switch sends a signal
to notify the controller of the floors to avoid during operation.
The following procedure describes how to set the number of floors the elevator is to avoid from
the bottom landing.
1. Navigate to MAIN MENU | SETUP | FLOOD. See Figure 60.
2. From the FLOOD menu, scroll and select Number of Floors.
Figure 609: FLOOD Menu – Number of Floors