C4 User Manual
October 25, 2021 ©2021 Smartrise Engineering, Inc. All Rights Reserved Page 299
3. From the RECALL KEY menu, scroll and select Flash Fire Hat.
Figure 585: RECALL KEY Menu – Flash Fire Hat
4. From the FLASH FIRE HAT menu, scroll and select On.
Figure 586: FLASH FIRE HAT Menu
5. Scroll right and press Save.
33.3.8 PIT Smoke
The PIT smoke is where the car is recalled to a designated landing when smoke has been
detected in the pit.
33.3.8.1 Main or Alternate
The car travels to the main landing when smoke has been detected. If configured and the
smoke is on that floor, the car travels to an alternated landing.
The following procedure describes if the car travels to the main or alternate designated landing
when smoke has been detected.
1. Navigate to MAIN MENU | SETUP | FIRE. See Figure 57.
2. From the FIRE SERVICE menu, scroll and select PIT Smoke.
Figure 587: FIRE SERVICE Menu – PIT Smoke