Page 308 ©2021 Smartrise Engineering, Inc. All Rights Reserved October 25, 2021
3. From the NUMBER OF FLOOD FLOORS menu, set the number of floors to avoid. For
example, a value of 001 would cause the elevator to avoid the bottom landing.
Figure 610: NUMBER OF FLOOD FLOORS MENU
4. Scroll right and press Save.
33.4.2 Okay to Run
The okay to run allows the elevator to continue running in automatic operation above the
floors that are flooded.
The following procedure describes how to allow the elevator to continue running above
flooded floors.
1. Navigate to MAIN MENU | SETUP | FLOOD. See Figure 60.
2. From the FLOOD menu, scroll and select Okay To Run.
Figure 611: FLOOD Menu – Okay To Run
3. From the OKAY TO RUN menu, scroll and select On to continue running in automatic
operation.
Figure 612: OKAY TO RUN Menu
4. Scroll right and press Save.
33.4.3 Override Fire
In emergency situations, it may be necessary to have flooding operation override fire operation.
The following procedure describes how to have flooding override fire.
1. Navigate to MAIN MENU | SETUP | FLOOD. See Figure 60.