4 Device control (DCTRL)
4.2 Device state machine and device states
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.2.7 OperationEnabled
The inverter is in this device status if the controller inhibit is deactivated and no error ("Trouble" or
"TroubleQSP") has occurred.
If the operation is enabled and the magnetisation in case of servo control (SC) and sensorless vector
control (SLVC) has been completed, the motor follows the setpoint determined by the active
application.
Depending on certain conditions, a status change takes place based on the "OperationEnabled"
device status.
Related topics:
wCANControl/wMCIControl control words
( 129)
"DRV-RDY" LED LED "DRV-ERR" Display in C00137 Display in status word 1 (C00150)
Bit 11 Bit 10 Bit 9 Bit 8
OFFOperationEnabled0101
Change condition Changeover to the device status
Control bit "EnableOperation" of a control channel = "0"
OR terminal RFR = LOW level (controller inhibit).
SwitchedOn
Control bit "SwitchOn" of a control channel = "0". ReadyToSwitchOn
Undervoltage in the DC bus. Trouble/Fault (depending on C00600/1)
Error with error response "Trouble" occurs. Trouble
Error with error response "TroubleQSP" occurs. TroubleQSP