10 Oscilloscope function
10.2 Operation
688
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
How to select a signal source for recording:
1. Double-click a non-assigned line in the channel list to open the Select signal source dialog
box.
Double-clicking an already pre-assigned selection enables you to assign it with another
signal source.
2. Select a new variable in the Select signal source dialog box.
3. Click the OK button.
The dialog box is closed and the selection is accepted.
How to delete a selection:
1. Go to the channel list and click the signal source to be removed.
2. Right-click the context menu to open it.
3. Select the Delete signal source command in the context menu.
You can add so many signal sources for recording until all acht channels are assigned.
10.2.3 Selecting the recording time/sample rate
How to define the sampling rate and time base for recording:
1. Select the desired time base from the time base list field.
The current time base setting multiplied by ten results in the recording time.
Since the measured value memory of the 8400 HighLine has a limited capacity, usually a
compromise is made between sample rate and recording time.
2. Enter the desired sampling rate in [ms] in the sampling rate input field.

Table of Contents

Other manuals for Lenze 8400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8400 and is the answer not in the manual?

Lenze 8400 Specifications

General IconGeneral
CategoryDC Drives
Series8400
Protection classIP20
Control TypeVector control
CommunicationCANopen, PROFIBUS, Ethernet
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature
Input VoltageAC 230/400/480 V

Related product manuals