5 Motor control (MCTRL)
5.10 Parameterisable additional functions
274
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.10.6.2 Oscillation damping in the field weakening range
When the max. possible output voltage (full modulation) has been reached, a voltage dip in the DC
bus causes a voltage fluctuation in the motor. With load and during no-load operation this voltage
fluctuation can cause mechanical oscillations.
The "oscillation damping field weakening" adjustable in C00236
serves to limit the maximum
output voltage. This can be used to always compensate voltage dips in the DC bus to the output
voltage (constant output voltage). This serves to prevent mechanical oscillations due to these
voltage dips.
With the Lenze setting of C00236
the limitation of the output voltage is set so that voltage dips
in the DC bus in the output voltage for the single-phase and three-phase devices can largely be
compensated so that no speed oscillations may be expected. Thus, an adaptation of C00236
is
not required in the majority of cases.
Maximum output voltage to be reached with Lenze setting of C00236
:
•Single-phase devices: 98.2%
Three-phase devices: 99.7 %
How to eliminate speed oscillations in the field weakening range:
1. Approach the area where the speed oscillations occur.
2. Reduce the speed oscillations by changing C00236
step by step (increment 1).
3. These can be indicators for smooth running:
Constant motor current characteristic
Reduction of the mechanical oscillations in the bearing seat
Parameters Info Lenze setting
Value Unit
C00236 Oscillation damping field weakening
•Setting "0" 100 % output voltage can be reached
14
Note!
The limitation of the output voltage via C00236 in the extreme field weakening range
(high speeds) causes a reduction of the max. possible output torque (stalling torque).
If the output torque to be reached in the extreme field weakening range is not
sufficient (motor is stalling too early), reduce the setting in C00236
.
With servo control (SC), the Lenze setting of C00236
should not be reduced. Otherwise
the field weakening control could not work optimally anymore (the behaviour at high
speeds may get worse). When servo control (SC) has been selected, the oscillation
damping in C00236
should never be set to "0".

Table of Contents

Other manuals for Lenze 8400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8400 and is the answer not in the manual?

Lenze 8400 Specifications

General IconGeneral
CategoryDC Drives
Series8400
Protection classIP20
Control TypeVector control
CommunicationCANopen, PROFIBUS, Ethernet
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature
Input VoltageAC 230/400/480 V

Related product manuals