_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.10.4.1 Manual DC-injection braking (DCB)
DC-injection braking can be activated manually for the two technology applications "speed
actuating drive" and "switch-off positioning" by connecting the bSetDCBrake input of the LA_NCtrl
or LA_SwitchPos application block to a digital signal source (e.g. via a digital signal source bCtrl1_B3
of the LP_CanIn1
port block).
• For HIGH-active inputs, DC-injection braking is active as long as the signal is at HIGH level.
•After the hold time (C00107
) has expired, the inverter set the pulse inhibit.
Short overview of the relevant configuration parameters:
5.10.4.2 Automatic DC-injection braking (Auto-DCB)
"Automatic DC-injection braking" (referred to in the following as "auto DCB") can be used if there is
a requirement that the drive be isolated from the supply at n
≈ 0.
Function
For understanding the auto DCB function, it is necessary to distinguish between three different
types of operation:
A. The drive has been enabled and, in the course of operation, the speed setpoint falls below the
auto DCB threshold.
• In case of V/f operation without
speed feedback, a braking current (C00036) is injected. After
the auto DCB hold time (C00106
) has expired, the motor is deenergised via the auto DCB
function, i.e. pulse inhibit is set.
• In case of V/f operation with
speed feedback, the motor is deenergised via the auto DCB
function after the auto DCB hold time (C00106
) has expired, i.e. pulse inhibit is set. The
braking current which can be parameterised in C00036
does not have any effect during
operation with speed feedback.
B. When the controller is enabled, the drive is at standstill (n = 0).
If the enabled drive is to start, the speed setpoint passed via the acceleration ramp must exceed
the auto DCB threshold (C00019
). Below this threshold, the motor will not be energised.
Parameters Info Lenze setting
C00701/4
LA_NCtrl: bSetDCBrake
• "Speed actuating drive" application: Selection of
the signal source for manually activating DC-
injection braking.
Dependent on the selected
control mode
C00761/4
LA_SwitchPos: bSetDCBrake
• "Switch-off positioning" application: Selection of
the signal source for manually activating DC-
injection braking.
Dependent on the selected
control mode
Note!
Deactivate automatic DC-injection braking when a holding brake is used!
• For this purpose, go to C00019
and set the auto DCB threshold to "0".
• Background: Controller inhibit is already activated by the Holding brake control
.
( 605)