5 Motor control (MCTRL)
5.14 Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.14.13 Encoder open-circuit monitoring
When does the open-circuit monitoring system respond?
The open-circuit monitoring will trigger if
an open circuit occurs in the encoder cable.
an extreme overload (e.g. blocked motor shaft) occurs during the start-up phase of the motor.
highly dynamic reversion of the motor occurs.
the motor still rotates at high speed in the "SC servo control ASM" mode when the controller
enabled.
Which measured values lead to an actuation of the open-circuit monitoring system?
The following measured values checked for plausibility lead to an actuation of the open-circuit
monitoring system:
1. If the total deviation between actual speed and setpoint speed is higher than f = 40 Hz for a time
> 0.1 s .
2. If the actual speed detected is f = 0 Hz or n = 0 rpm and the I
max
controller or the torque
limitation for servo control (SC) is active for t 0.1 s.
3. If the sign of the injected frequency and the actual speed is not the same, the I
max
controller is
active and this status is active for 0.1 s. Usually this is the case when A/B tracks are reversed.
Response to open circuit
If the open-circuit monitoring is tripped:
The error response set in C00586
is activated (Lenze setting: "Fault").
•The "Sd3: Open circuit - feedback system
" is entered into the Logbook.
•The bMctrlEncoderComFault status output of the LS_DeviceMonitor
SB is set to TRUE.
A setting of C00586
= "0: No Reaction" deactivates the monitoring.
Related topics:
Encoder/feedback system
( 276)
Note!
In the Lenze setting (C00586 = "1: Fault"), open-circuit monitoring of the encoder is
activated!

Table of Contents

Other manuals for Lenze 8400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8400 and is the answer not in the manual?

Lenze 8400 Specifications

General IconGeneral
CategoryDC Drives
Series8400
Protection classIP20
Control TypeVector control
CommunicationCANopen, PROFIBUS, Ethernet
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature
Input VoltageAC 230/400/480 V

Related product manuals