5 Motor control (MCTRL)
5.5 V/f characteristic control - energy-saving (VFCplusEco)
180
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.5.4 Optimising the control mode
The V/f characteristic control - energy-saving (VFCplus) is generally ready for operation. It can be
adapted subsequently by adapting the characteristic and/or the drive behaviour.
Adapting characteristic
For the linear characteristic as part of the V/f characteristic control - energy-saving (VFCplusEco), it
is also possible (like in case of the standard V/f characteristic control) to match its curve to different
load profiles or motors by adapting the V/f base frequency (C00015
) and the V
min
boost (C00016).
Adapting the V/f base frequency
( 164)
Adapting the Vmin boost
( 166)
Adapting drive behaviour
• Limitation of the maximum current by a current limitation controller (e.g. to prevent the motor
from stalling or to limit to the maximally permissible motor current).Optimising the Imax
controller ( 167)
• Adaptation of the field frequency by a load-dependent slip compensation (improved speed
accuracy for systems without feedback).
• Improving the behaviour at high dynamic load changes
. ( 181)
• Adapting the slope limitation for lowering the Eco function
. ( 182)
• Optimising the cos/phi controller
. ( 182)
Torque limitation
Limit the torque to a lower value.Torque limitation
( 169)
Note!
Following successful motor parameter identification, the V/f base frequency (C00015)
and the V
min
boost (C00016) as well as the slip constant for slip compensation (C00021)
are calculated automatically.
From version 12.00.00 onwards:
• Following successful motor parameter identification, the gain of the Imax controller
(C00073/1
) is calculated automatically.
• If these parameters are not
to be calculated, bit 4 of C02865/1 must be set to "1".
• Following successful motor parameter identification, other controller parameters
(C00011
, C00022, C00966, C00982) can be calculated automatically.
• If these parameters are to be calculated, bit 6 of C02865/1
must be set to "6".