5 Motor control (MCTRL)
5.4 V/f characteristic control (VFCplus)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.4.3 Optimising the control mode
The V/f characteristic control (VFCplus) is generally ready for operation. It can be adapted
subsequently by adapting the characteristic and/or the drive behaviour.
Adapting characteristic
For the linear and quadratic characteristic, it is also possible to match its curve to different load
profiles or motors by adapting the V/f base frequency (C00015
) and the V
min
boost (C00016).
Adapting the V/f base frequency
( 164)
Adapting the Vmin boost
( 166)
Freely defining the characteristic
From version 04.00.00 onwards, the V/f characteristic can also be defined freely if the linear and
square-law characteristic are not suitable.
Defining a user-defined V/f characteristic
( 171)
Adapting drive behaviour
• Limitation of the maximum current by a current limitation controller (e.g. to prevent the motor
from stalling or to limit to the maximally permissible motor current).Optimising the Imax
controller ( 167)
• Adaptation of the field frequency by a load-dependent slip compensation (improved speed
accuracy for systems without feedback)
• Adaptation of the controller parameters of the slip regulator if V/f control (VFCplus + encoder)
is selected. Parameterising the slip regulator
( 189)
Note!
Following successful motor parameter identification, the V/f base frequency (C00015)
and the V
min
boost (C00016) as well as the slip constant for slip compensation (C00021)
are calculated automatically.
From version 12.00.00:
• Following successful motor parameter identification, the gain of the Imax controller
(C00073/1
) is calculated automatically.
• If these parameters are not
to be calculated, bit 4 of C02865/1 must be set to "1".
• Following successful motor parameter identification, other controller parameters
(C00011
, C00022, C00966) can be calculated automatically.
• If these parameters are to be calculated, bit 6 of C02865/1
must be set to "6".