Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23 731
11 System bus "CAN on board"
11.8 Process data transfer
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.8.3 Transmission type
Process data objects can be transmitted in an event-controlled or time-controlled manner. The
below table shows that it is possible to combine the different methods by means of logic operations
(AND, OR):
•Event-controlled
The PDO is sent when a special device-internal event has occurred, e.g. when the data contents
of the TPDO have changed or when a transmission cycle time has elapsed
Synchronous transmission
A TPDO (or RPDO) is transmitted (or received) after the device has received a sync telegram
(COB-ID 0x80).
Cyclic transmission
The cyclic transmission of PDOs takes place when the transmission cycle time has elapsed.
Polled via RTR
A TPDO is transmitted when another device requests it by means of a data request telegram
(RTR remote transmit request). For this purpose, the data requester (e.g. the master) sends the
data request telegram with the COB-ID of the TPDO requested to be sent. The receiver
recognises the RTR and transmits the corresponding PDO.
Transmission type PDO transmission Logic combination of
different
transmission types
cyclic synchronous event-controlled
0 AND
1 ... 240 -
254, 255 OR
Transmission type Description
0 Synchronous and acyclic:
The PDO is transmitted on an event-controlled basis with every sync (e.g. when a bit change
occurs in the PDO).
1 ... 240 Synchronous and cyclic (sync-controlled with response):
Selection n = 1: The PDO is transmitted with every
sync.
Selection 1 < n 240: The PDO is transmitted with every n-th
sync.
From version 16.00.00 onwards, the transmit PDOs are also sent when the sync telegram is
generated. Precondition: the sync Tx identifier and sync Rx identifier have the same value.
241 ... 251 Reserved
252 Synchronous - RTR only
253 Asynchronous - RTR only
254, 255 Asynchronous - manufacturer-specific / device profile-specific:
If this value is entered, the PDO transmission is event-controlled or
cyclic.
(Note: The values "254" and "255" have the same meaning).
For a cyclic transmission, a cycle time must be entered for the respective PDO. In this case,
cyclic transmission takes place in addition to event-controlled transmission.

Table of Contents

Other manuals for Lenze 8400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8400 and is the answer not in the manual?

Lenze 8400 Specifications

General IconGeneral
CategoryDC Drives
Series8400
Protection classIP20
Control TypeVector control
CommunicationCANopen, PROFIBUS, Ethernet
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature
Input VoltageAC 230/400/480 V

Related product manuals