EasyManuals Logo

Lenze 8400 User Manual

Lenze 8400
1590 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #275 background imageLoading...
Page #275 background image
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23 275
5 Motor control (MCTRL)
5.10 Parameterisable additional functions
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.10.7 Phase sequence reversal for correcting misconnected UVW motor phases
This function extension is only available from version 04.00.00!
If the motor phases are misconnected at the inverter output (e.g. phase u takes the place of phase
v), the motor will rotate in the wrong direction.
To correct such misconnected motor phases, the rotating field of the inverter's output can be
reversed by selecting "1: Inverted" in C00905
. In this case, a phase will be reversed at the output of
the inverter.
This function does not have any effect on setpoints and actual values, i.e. the polarity of the speed
setpoint/actual speed value, actual torque, output frequency, and AngleOffset do not change.
Tip!
Cases of application for this function:
Phase sequence reversal in case of misconnected motor phases.
Setting of the correctly signed direction of rotation for inversely mounted motors.
Note!
Up to and including version 11.00.00, this function may only be activated for the
following motor control types:
V/f characteristic control (VFCplus)
( 157)
V/f characteristic control - energy-saving (VFCplusEco)
( 175)
For all other motor control types, this function must not be activated because the set
control mode would not work in that case!
From version 12.00.00, this function may be activated for all motor control types with
the exception of the ones for synchronous motor.
The activation of this function does not affect the control types for synchronous motor
since these control types require an in-phase connection of the synchronous motor.

Table of Contents

Other manuals for Lenze 8400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8400 and is the answer not in the manual?

Lenze 8400 Specifications

General IconGeneral
CategoryDC Drives
Series8400
Protection classIP20
Control TypeVector control
CommunicationCANopen, PROFIBUS, Ethernet
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature
Input VoltageAC 230/400/480 V