4 Device control (DCTRL)
4.2 Device state machine and device states
122
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.2.10 Fault
This device status will be active as soon as a monitoring mode responds the error response "Fault"
has been parameterised for.
The motor has no torque (is coasting) when the inverter is inhibited.
The error must explicitly be reset ("acknowledged") in order to exit the device status, e.g. by the
device command "Reset error
" or via the control bit "ResetFault" in the control word
wCanControl or wMCIControl.
Related topics:
wCANControl/wMCIControl control words
( 129)
Basics on error handling in the inverter
( 623)
Error messages of the operating system
( 647)
4.2.11 SystemFault
This device state is not used since the inverter lacks the activating event.
This device status becomes active if a system fault occurs.
The device status can only be abandoned by
•mains switching or
a system restart.
"DRV-RDY" LED LED "DRV-ERR" Display in C00137 Display in status word 1 (C00150)
Bit 11 Bit 10 Bit 9 Bit 8
OFF Fault 1000
Note!
If an undervoltage in the DC bus of the inverter occurs (error message "LU"), the device
changes to the "Trouble
" status.
An additional error of higher priority leads the device into the "Fault
" status.
According to the Device state machine
, the device changes to the "ReadyToSwitchOn"
status after acknowledging the error although the undervoltage is still available!
If the "Inhibit at fault" auto-start option has been activated in C00142
, explicit
deactivation of the controller inhibit is required before the status can be abandoned.
"DRV-RDY" LED LED "DRV-ERR" Display in C00137 Display in status word 1 (C00150)
Bit 11 Bit 10 Bit 9 Bit 8
OFF SystemFault 1011

Table of Contents

Other manuals for Lenze 8400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8400 and is the answer not in the manual?

Lenze 8400 Specifications

General IconGeneral
CategoryDC Drives
Series8400
Protection classIP20
Control TypeVector control
CommunicationCANopen, PROFIBUS, Ethernet
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature
Input VoltageAC 230/400/480 V

Related product manuals