4 Device control (DCTRL)
4.2 Device state machine and device states
122
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.2.10 Fault
This device status will be active as soon as a monitoring mode responds the error response "Fault"
has been parameterised for.
• The motor has no torque (is coasting) when the inverter is inhibited.
• The error must explicitly be reset ("acknowledged") in order to exit the device status, e.g. by the
device command "Reset error
" or via the control bit "ResetFault" in the control word
wCanControl or wMCIControl.
Related topics:
wCANControl/wMCIControl control words
( 129)
Basics on error handling in the inverter
( 623)
Error messages of the operating system
( 647)
4.2.11 SystemFault
This device state is not used since the inverter lacks the activating event.
This device status becomes active if a system fault occurs.
• The device status can only be abandoned by
•mains switching or
• a system restart.
"DRV-RDY" LED LED "DRV-ERR" Display in C00137 Display in status word 1 (C00150)
Bit 11 Bit 10 Bit 9 Bit 8
OFF Fault 1000
Note!
If an undervoltage in the DC bus of the inverter occurs (error message "LU"), the device
changes to the "Trouble
" status.
An additional error of higher priority leads the device into the "Fault
" status.
According to the Device state machine
, the device changes to the "ReadyToSwitchOn"
status after acknowledging the error although the undervoltage is still available!
If the "Inhibit at fault" auto-start option has been activated in C00142
, explicit
deactivation of the controller inhibit is required before the status can be abandoned.
"DRV-RDY" LED LED "DRV-ERR" Display in C00137 Display in status word 1 (C00150)
Bit 11 Bit 10 Bit 9 Bit 8
OFF SystemFault 1011